Crossref DOIMemberCiteFactoropen accessissn
SJIF Impact Factor 8.659 | ISSN: 2582-3930
IJSREM Logo

International Journal of Scientific Research in Engineering and Management

(Gateway to Global Scholars - An International, Scholarly, Multi-Disciplinary, Open Access Journal)

Peer-Reviewed Journal Designed to Meet UGC's Quality Parameters

HomeCurrent IssuePast IssuesPay OnlineConferencesEditorial BoardAbout UsContact Us
IJSREM

Loading article...

Follow Us

  • Google Scholar
  • ResearchGate
  • Academia.edu
  • Mendeley
  • LinkedIn
  • Facebook
  • Instagram

Journal Policies

  • Peer Review Policy
  • Publication Ethics
  • Copyright Infringement
  • Refund & Cancellation Policy
  • Terms and Conditions
  • Privacy Policy

Journal Identifiers & Licenses

  • ISSN Verified: 2582-3930ISSN Verified: 2582-3930
  • Crossref DOI: 10.55041Crossref DOI: 10.55041
  • SJIF Ranking: 08.659SJIF Ranking: 08.659
  • Licensed under CC BY 4.0Licensed under CC BY 4.0
  • ISO Certification: 9001:2015ISO Certification: 9001:2015
  • Indexed & Cited In: Google ScholarIndexed & Cited In: Google Scholar

Contact Us

International Journal of Scientific Research in Engineering and Management (IJSREM)

#62/1, New No 7, 1st Cross, 2nd Main, Ganganagar, R T Nagar, Bangalore North, Bangalore, Karnataka, India – 560032
[email protected]+91 93911 67991
logos
logos
Working Hours

Mon – Sat: 9:00 AM – 6:00 PM

Sunday: 10:00 AM – 4:00 PM

+91 93911 67991

© 2026 IJSREM – International Journal of Scientific Research in Engineering and Management. This is an open-access journal. Articles are published under the Creative Commons Attribution (CC BY 4.0) License, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.

DisclaimerPrivacy PolicyTerms and Conditions
ArticlePeer ReviewedOpen AccessPlagiarism Passed
Paper ID:IJSREM68799

Comparative Analysis of Wind Load Effects on a G+10 RCC Building for Different Basic Wind Speeds Using STAAD.Pro

Stream/Area:

-

Subject:

-

Paper ID:

IJSREM68799

Volume:

10 |

11 |

Nov 2026

Pages:

1-11

Publication Frequency:

Monthly (12 issues per year)

DOI
Digital Object Identifier
10.55041/IJSREM68799

License:International Journal of Scientific Research in Engineering and Management follows the Creative Commons Attribution 4.0 (CC BY 4.0) License, allowing free use and distribution with proper attribution.

Share this article:

Authors

BPP

B. PURNA PRUDHVI

Civil Engineering

Sanketika Vidya Parishad Engineering College

Download Author Certificate

Mentors

BPR

B. PRUDVI RANI

Assistant Professor, Department of Civil Engineering,

Sanketika Vidya Parishad Engineering College, P.M. Palem, Visakhapatnam – 530041, Andhra Pradesh, India

Download Mentor Certificate

Author Services & Downloads

Full ArticlesAcceptance Certificate

Abstract

Wind pressure on a building varies with the square of the design wind speed, so the same building plan can attract very different lateral load demands in different wind regions of India. This study evaluates a regular G+10 reinforced cement concrete (RCC) moment-resisting framed building, 24 m × 18 m in plan on a 6 m × 6 m grid, modelled in STAAD.Pro and analysed under dead, live and wind loads according to IS 875 (Parts 1–3) and IS 456:2000. Three basic wind speeds of 39, 47 and 55 m/s were applied along both principal directions, with the geometry, sections, materials, supports and gravity loads kept identical. For the 39 m/s case, the base shear was 625.8 kN for wind along X and 834.4 kN for wind along Z, with overturning moments of 11,046 and 14,728 kN·m. Every wind-induced response, including the support reactions, base shear, overturning moment and beam end forces, increased by 45.2% at 47 m/s and by 98.9% at 55 m/s. These increases equal the ratio of the squared wind speeds, as expected for a linear static analysis. The wind-induced axial reaction of the corner column rose from 132.3 to 263.1 kN. The wind combination 1.5(DL + WL) governed the end moment of a typical 6 m beam at all three speeds, giving 140.7, 167.6 and 199.6 kN·m, compared with 97.5 kN·m under 1.5(DL + LL). For the corner column, the gravity combination governed at 39 and 47 m/s, but at 55 m/s the wind combination exceeded it by 2.9%. No uplift occurred under 0.9DL − 1.5WL. The results show that a building designed for one wind speed cannot be reused at a higher-wind site without re-checking its beams and columns.

KEYWORDS

RCC framed building; Wind load; IS 875 (Part 3); Basic wind speed; STAAD.Pro; Base shear; Overturning moment; Load combinations

Cite This Article

B. PURNA PRUDHVI, B. PRUDVI RANI, "Comparative Analysis of Wind Load Effects on a G+10 RCC Building for Different Basic Wind Speeds Using STAAD.Pro," International Journal of Scientific Research in Engineering and Management, vol. 10, no. 11, pp. 1-11, Nov 2026. https://doi.org/10.55041/IJSREM68799

Full Article/Conclusion

1.      A G+10 RCC framed building, 24 m × 18 m in plan, was analysed in STAAD.Pro for basic wind speeds of 39, 47 and 55 m/s according to IS 875 (Part 3):2015, keeping all other parameters unchanged. The gravity loads totalled 54,520.7 kN (DL), 8640 kN (LL) and 648 kN (roof LL). 2.      At 39 m/s the base shear was 625.8 kN for wind along X and 834.4 kN for wind along Z, in the ratio of the exposed faces (24/18). The overturning moments were 11,046 and 14,728 kN·m, with the resultant acting 17.65 m above the base. 3.      All wind-induced responses increased by 45.2% at 47 m/s and by 98.9% at 55 m/s, exactly in proportion to the square of the basic wind speed. At 55 m/s the base shear reached 1659.5 kN and the overturning moment 29,292 kN·m. 4.      The wind-induced axial reaction of the corner column increased from 132.3 to 263.1 kN (7.5% to 15.0% of its dead-load reaction). The gravity combination governed the column at 39 and 47 m/s, but at 55 m/s the combination 1.5(DL + WL) governed, at 3032.1 kN. No uplift occurred at the base. 5.      Wind governed the beam design at every wind speed. The factored end moment of a 6 m beam under 1.5(DL + WL) was 140.7, 167.6 and 199.6 kN·m, which is 44% to 105% above the gravity value. Beam deflections were not significantly affected by wind speed. 6.      A building plan designed for one wind speed should not be repeated at a higher-wind site without re-checking the beams and columns, particularly the end moments of beams in the lower storeys and the corner columns.

References

[1]       Sk. Amiruddin, P. Lakshmana, S. Dinesh Karthik, and K. Ganesh, "Analysis of residential building subjected to wind load using STAAD Pro," Journal of Emerging Trends and Novel Research, vol. 4, no. 3, 2026. [2]       Keshav and Rajbala, "Dynamic modeling and performance assessment of RCC vs. steel structures subjected to seismic and wind loads," International Journal of Research in Civil Engineering and Technology, 2025, doi: 10.22271/27078264.2025.v6.i2b.118. [3]       A. Saxena et al., "Examination of wind impacts on RCC frame structures in different wind zones," E3S Web of Conferences, vol. 529, Art. no. 01011, 2024, doi: 10.1051/e3sconf/202452901011. [4]       C. Siddartha, D. Sathwika, G. Pramod, and G. Haritha, "Analysis and design of tall building subjected to wind and earthquake loads by using STAAD.PRO," 2024, doi: 10.5281/zenodo.14267042. [5]       B. D. Yadav, N. Choudhary, J. K. Mahato, and N. Kumar, "Study the effects of various wind loadings in high rise RC-framed structures in Zone–V," Journal of Civil Engineering Research & Technology, vol. 5, no. 1, 2023, doi: 10.47363/JCERT/2023(5)139. [6]       A. Jain, S. Tyagi, P. Singh, P. Sachan, S. Prakash, and S. Dev, "Wind analysis and design of G+5 building using STAAD.Pro," International Journal for Research Trends and Innovation, vol. 8, no. 5, 2023. [7]       M. Shahraz, M. D. Hasnain, and A. H. Siddiqui, "Comparative study on analysis of G+10 regular residential building subjected to wind load by STAAD.Pro V8i and ETABS 2020 software's," International Research Journal of Engineering and Technology, vol. 9, no. 12, 2022. [8]       K. V. Vinay, N. Kavya, B. Praveen Yadav, M. Gowtham, and N. Raghavendra, "Wind analysis and design of G+5 residential building using STAAD.Pro," International Journal of Innovative Research in Science, Engineering and Technology, vol. 9, no. 7, 2020. [9]       IS 875 (Part 1):1987, Code of Practice for Design Loads (Other Than Earthquake) for Buildings and Structures – Part 1: Dead Loads, Bureau of Indian Standards, New Delhi. [10]    IS 875 (Part 2):1987, Code of Practice for Design Loads (Other Than Earthquake) for Buildings and Structures – Part 2: Imposed Loads, Bureau of Indian Standards, New Delhi.

Editorial & Review Transparency

Publication Date

11/6/2026

Peer Review Type

Double-Blind Peer Review

Review Rounds: 2

Documents

Review Report (Confidential)
Copyright Form (Office)

Article Metrics & Impact

Article Views

0

Total views since publication

PDF Downloads

4

Total downloads since publication

Geographic Reach

5

Indexing, Archiving & Preservation

Google Scholar
Academia
ResearchGate
Crossref
SSRN
Semantic Scholar
Thomson Reuters
WorldCat
Mendeley
OpenAlex
EBSCO
Zenodo

Digital Preservation: This article is permanently archived on Zenodo and complies with all data preservation standards across major indexing platforms.

Ethics, Compliance & Transparency

Plagiarism Screening

This manuscript has been checked for plagiarism using TurnitinPlagiarismChecker software.

Conflict of Interest

The authors declare no conflict of interest related to this research work.

Funding Information

No funding information available for this research.

Similar & Recommended Articles

Similar Articles by Topic

Related research in the same subject area

Loading similar articles...